Emergency Lighting Installation and Testing for Businesses in Cardiff and South Wales
If the power fails, people in your building need enough light to find the way out. Emergency lighting is a legal requirement in almost every non domestic building and in the common parts of blocks of flats, and it has to be tested regularly. VOG Fire & Security designs, installs, tests and certifies emergency lighting to BS 5266-1 across the Vale of Glamorgan and South Wales, usually alongside the fire alarm so both are serviced together. Call 01446 739586.
Book emergency lighting testingDoes your premises need emergency lighting?
Yes if the public or staff use the building and could be inside when the lights fail. The Regulatory Reform (Fire Safety) Order 2005 requires escape routes to be adequately lit where needed, and BS 5266-1 sets out how. In practice you need emergency lighting on all escape routes, at every change of direction and level, at fire exits and fire equipment, in open areas over 60 square metres, in toilets over 8 square metres, in plant rooms and in lifts. The common stairways and corridors of blocks of flats also need it.


What types of emergency lighting are there?
- Maintained: the fitting is on all the time as normal lighting and stays on from battery when the power fails. Used in places like cinemas, pubs and venues where normal lighting is dimmed.
- Non maintained: the fitting stays off until the power fails, then comes on from battery. The usual choice for offices, shops and corridors.
- Self contained: each fitting has its own battery. Simplest to install and the most common option.
- Central battery: one battery bank powers all fittings. Used in larger buildings where fittings are hard to reach for maintenance.
- Exit signs: illuminated running man signs at every final exit and along the route.
- Self testing fittings: run their own monthly and annual tests and show a fault light, cutting the cost of manual testing.
All fittings are rated for three hours, which is the standard duration required in most buildings.

How often must emergency lighting be tested?
Monthly and annually. BS 5266-1 requires a short functional test every month, where each fitting is switched to battery to confirm it lights, and a full three hour discharge test once a year, where every fitting must stay lit for its full rated duration. Both must be recorded in a log book. The annual test should be carried out by a competent person, and any fitting that fails must be repaired or replaced. Self testing fittings do the tests automatically but the results still have to be checked and recorded.
VOG carries out annual emergency lighting testing and certification across Cardiff, Barry, Bridgend, Penarth, Cowbridge, Llantwit Major and Caerphilly, usually on the same visit as the fire alarm service.
What affects the cost of emergency lighting?
The number of fittings needed, which depends on the size and layout of the building, whether fittings are self contained or central battery, whether you want self testing units, and how easy it is to reach the existing lighting circuits. Where new fittings are needed the survey produces a lighting design and a written quote. For testing only, the cost is based on the number of fittings.
How is emergency lighting installed?
The engineer surveys the building against BS 5266-1, produces a plan showing where fittings and signs are required, and installs them on the local lighting circuit with a test key switch where needed. On completion the whole system is discharge tested, a completion certificate and log book are issued, and you are shown how to carry out the monthly test.
Where does VOG install and test emergency lighting?
Across Cardiff, Barry, Bridgend, Penarth, Cowbridge, Llantwit Major, Caerphilly and the rest of the Vale of Glamorgan and South Wales.